# EN 61508 — Functional Safety of E/E/PE Systems
|
||
|
||
## Overview
|
||
|
||
EN 61508 is the generic functional safety standard for Electrical / Electronic / Programmable Electronic (E/E/PE) systems.
|
||
|
||
It provides a framework to ensure systems reduce risk to an acceptable level.
|
||
|
||
---
|
||
|
||
## Core Idea
|
||
|
||
Risk is defined as:
|
||
|
||
Risk = Frequency × Consequence
|
||
|
||
Safety functions reduce this risk.
|
||
|
||
---
|
||
|
||
## Key Concepts
|
||
|
||
### Safety Function
|
||
A function that:
|
||
- Detects hazardous conditions
|
||
- Takes action to prevent harm
|
||
|
||
---
|
||
|
||
### Safety Integrity Level (SIL)
|
||
|
||
| SIL | Meaning |
|
||
|-----|--------|
|
||
| SIL 1 | Low risk reduction |
|
||
| SIL 2 | Moderate |
|
||
| SIL 3 | High |
|
||
| SIL 4 | Very high |
|
||
|
||
---
|
||
|
||
### Probability of Failure
|
||
|
||
#### Low Demand Mode (PFDavg)
|
||
|
||
| SIL | Range |
|
||
|-----|-------|
|
||
| SIL 1 | 1e-2 to 1e-1 |
|
||
| SIL 2 | 1e-3 to 1e-2 |
|
||
| SIL 3 | 1e-4 to 1e-3 |
|
||
| SIL 4 | 1e-5 to 1e-4 |
|
||
|
||
#### High/Continuous Mode (PFH)
|
||
|
||
| SIL | Failures/hour |
|
||
|-----|---------------|
|
||
| SIL 1 | 1e-6 to 1e-5 |
|
||
| SIL 2 | 1e-7 to 1e-6 |
|
||
| SIL 3 | 1e-8 to 1e-7 |
|
||
| SIL 4 | 1e-9 to 1e-8 |
|
||
[[PFD_PFH_when_to_use]]
|
||
|
||
[[PFD_and_PFH]]]
|
||
|
||
---
|
||
|
||
## Safety Lifecycle
|
||
|
||
1. Hazard analysis
|
||
2. Safety requirements
|
||
3. System design
|
||
4. Hardware design
|
||
5. Software design
|
||
6. Verification & validation
|
||
7. Operation & maintenance
|
||
8. Decommissioning
|
||
|
||
---
|
||
|
||
## Hardware Reliability
|
||
|
||
- FIT = 1e-9 failures/hour
|
||
- PFH = Probability of dangerous failure/hour
|
||
- PFDavg = Probability of failure on demand
|
||
|
||
---
|
||
|
||
## Failure Types
|
||
|
||
### Random Failures
|
||
Handled statistically (FIT, PFH)
|
||
|
||
### Systematic Failures
|
||
Handled by process, reviews, and discipline
|
||
|
||
---
|
||
|
||
## Techniques
|
||
|
||
- Redundancy (1oo2, 2oo3)
|
||
- Diagnostics
|
||
- Diversity
|
||
- Formal methods (high SIL)
|
||
|
||
---
|
||
|
||
## Standard Structure
|
||
|
||
1. General
|
||
2. Hardware
|
||
3. Software
|
||
4. Definitions
|
||
5–7. Guidelines
|
||
|
||
---
|
||
|
||
## Related Standards
|
||
|
||
- EN 61511 (Process)
|
||
- EN 62061 (Machinery)
|
||
- ISO 26262 (Automotive)
|
||
- EN 298 (Burners)
|
||
|
||
---
|
||
|
||
## Key Takeaways
|
||
|
||
- Focus on risk reduction
|
||
- SIL is a target, not a feature
|
||
- Process matters as much as maths
|
||
- Lifecycle coverage is essential
|
||
|
||
---
|
||
|
||
## One-Line Summary
|
||
|
||
EN 61508 ensures safety systems reduce risk using quantified reliability and disciplined engineering processes.
|
||
|
||
---
|
||
|